Descrizione
For the control of fan coil units. Via two analog outputs, two analog valves or one 6-way valve drive can be controlled for heating and cooling. For the fan control the devices features an analog output for the control of a continues fan. A relay output switches an additional load of up to 16 A, such as auxiliary heating. Over 4 inputs the room status can be detected and monitored (Use for window contact, dew point sensor, level sensor or temperature sensor). Also it is possible to connect one analog room control unit (SAR/A or SAF/A) to the inputs of the device. The device has an integrated room temperature controller for the control of the room temperature, which can be used directly to control the outputs of the device. The device supports the ABB i-bus Tool for advanced diagnosis and improved commissioning.
EU Declaration of Conformity - ABB2CDG110214R0011
Deeplink REACH - ABB2CDG110214R0011
Caratteristiche tecniche
tipo di montaggio
AMD
numero di uscite
4
sistema bus EIB/KNX
SI
sistema bus radio
NO
accoppiamento bus incluso
SI
numero di ingressi digitali
4
larghezza in unità di suddivisione
6
altri sistemi bus
Senza
tensione di commutazione (V)
0
grado di protezione (IP)
IP20
grandezza regolante costante
SI
grandezza regolante commutante
SI
funzione di protezione valvola
SI
commutazione manuale
SI
radio bidirezionale
NO